Service Menu: Sensor Calibration/ Setup Parameters S600 series:
Page 1 of 3
Menu Line Parameter Range
S601 Password -
S602 Return temperature ±17ºF
S603 Calibrated return temperature 32 - 122ºF
S604 Return humidity ±9.9%
S605 Calibrated return humidity 20 – 80%
S606 Digital Scroll 1 NTC ±17ºF
S607 Calibrated digital scroll 1 NTC 84 – 313ºF
S608 Digital Scroll 2 NTC ±17ºF
S609 Calibrated digital scroll 2 NTC 84 - 313ºF
Service Menu: Sensor Calibration/ Setup Parameters: Page 2 of 3
Menu Line Parameter Range
S612 Password -
S613 Temperature sensor A ±17ºF
S614 Calibrated temperature sensor A 32 - 122ºF
S615 Humidity sensor A ±9.9%
S616 Calibrated humidity sensor A 20 – 80%
S617 Temperature sensor B ±17ºF
S618 Calibrated temperature sensor B 32 - 122ºF
S619 Humidity sensor B ±9.9%
S620 Calibrated humidity sensor B 20 – 80%