Liebert iCOM Microprocessor TM-10098 Manual de usuario Pagina 69

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 170
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 68
iCOM
Controls Training and Service Manual
Service Menu: Set Point Parameters S100 series: Page 2 of 2
Menu Line Parameter Default Range
S112 Password - -
S113 Humidity Proportional Band 10% 1 – 20%
S114 Humidity Integration Time 0 0 – 5 minutes
S115 Humidity Deadband 0 0 – 50%
S116 DT Between Room / FC Type Disable
Disable, Contact,
Value
S117 DT Between Room Air / FC Fluid 8ºF 0 - 36ºF
S118 Minimum CW Temp Disable Enable / Disable
S119 Minimum CW Temp Value 45ºF 32 - 68ºF
S120
S121
S122
Service Menu: Unit Diary Log
Parameter
Displays changes to the unit as performed and entered by
the service person or customer
68
Vista de pagina 68
1 2 ... 64 65 66 67 68 69 70 71 72 73 74 ... 169 170

Comentarios a estos manuales

Sin comentarios