iCOM
Controls Training and Service Manual
Setting Parameters
Example: 2 Units with Small Display’s
All Network parameters are viewed and programmed using the
Service Menu function and by selecting the Network Setup Icon
The following example references menu lines on the Network Setup screen:
Line S802: Number units connected: xx (2)
Line S803: Teamwork: xx (No, 1, 2)
Line S804: Control Board IP Address: 192.168.254. xxx (010, 011)
Line S805: Control Board Netmask IP the same for all units
Line S806: Control Board Gateway IP the same for all units
Line S808: U2U address Control Board #: xx (1-2)
Line S810: U2U group #: xx (1)
Unit No. 2
Unit No. 1
U2U: CAT5 (Crossover-cable)