Control Training and Service Manual
Service Menu: Compressor 2 Settings Maintenance / Wellness Parameters:
Page 4 of 8
Menu Line Parameter Default Range
S034 Password - -
S035 Number of Starts - 0 – 32000
S036 Run Hours - 0 – 32000
S037 Average Working Time - 0 – 999 minutes
S038 Starts per Day Optimum 12 1 – 240
S039 Starts per Day Worst 240 1 – 240
S040 Number of HP Alarms - 0 – 32000
S041 Number of LP Alarms - 0 – 32000
S042 Number of OL Alarms - 0 – 32000
S043 Number of DS HT Alarms - 0 - 32000
S044 Actual Bonus - 0 - 12
Service Menu: Electric Heater 1 Settings Maintenance / Wellness
Parameters: Page 5 of 8
Menu Line Parameter Default Range
S045 Password - -
S046 Number of Starts - 0 – 32000
S047 Run Hours - 0 – 32000
S048 Average Run Time - 0 – 999 minutes
S049 Starts per Day Optimum 24 1 – 240
S050 Starts per Day Worst 240 1 – 240
S051 Number of Alarms - 0 – 32000
S052 Actual Bonus - 0 - 12