iCOM
Controls Training and Service Manual
Example: Large Wall Display and Five Units with Small Displays
All Network parameters are viewed and programmed using the
Service Menu function and by selecting the Network Setup Icon
The following example references menu lines on the Network Setup screen:
Line S802: Number units connected: xx (01 - 32)
Line S803: Teamwork: xx (No, 1, 2)
Line S804: Large Display Board IP Address: 192.168.254. xxx (001 - 049)
Line S804: Control Board IP Address: 192.168.254. xxx (050 - 099)
Line S804: Wall Mount (LBB) IP Address: 192.168.254. xxx (100 - 149)
Line S806: Large Display Board Gateway IP: 192.168.254.255
Line S806: Control Board Gateway IP: 192.168.254.255
Line S808: U2U address Display #: xx (33 - 64)
Line S808: U2U address Control Board #: xx (01 - 32)
Line S810: U2U group #: xx (01 - 99)
U2U:
Switc
46