Liebert iCOM Microprocessor TM-10098 Manual de usuario Pagina 64

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 170
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 63
iCOM
Control Training and Service Manual
User Menu: Set Alarm Parameters U200 series
Menu Line Parameter Default Range
U201 Password - -
U202 Return Sensor Alarms Enabled Enabled or Disabled
U203 High Return Temperature 80ºF 33 - 210ºF
U204 Low Return Temperature 60ºF 33 - 210ºF
U205 High Return Humidity 60% 1 – 99%
U206 Low Return Humidity 40% 1 – 99%
U207 Sensor A Alarms Disabled Disabled or Enabled
U208 High Temperature Sensor A 90ºF 33 - 210ºF
U209 Low Temperature Sensor A 55ºF 33 - 210ºF
U210 High Humidity Sensor A 70% 1 - 99%
U211 Low Humidity Sensor A 30% 1 - 99%
User Menu: Sensor Data U300 series: Page 1 of 2
Menu Line Parameter Range
U301 Actual Temperature Setpoint 41 – 104ºF
U302 Actual Humidity Setpoint 20 – 80%
U303 Optional Sensor A Temperature 32 - 122ºF
U304 Optional Sensor A Humidity 20 – 80%
U305 Optional Sensor B Temperature 32 - 122ºF
U306 Optional Sensor B Humidity 20 – 80%
U307 Optional Sensor C Temperature 32 - 122ºF
U308 Optional Sensor C Humidity 20 – 80%
U309 Freecooling Fluid Temperature 4 - 113ºF
U310 DigiScroll 1 Temperature 84 - 313ºF
U311 DigiScroll 2 Temperature 84 - 313ºF
U312
Freecooling Status Off, Start, On
63
Vista de pagina 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 169 170

Comentarios a estos manuales

Sin comentarios