iCOM
Control Training and Service Manual
Service Menu: Standby Setting / Lead-lag Parameters S500 series
Menu Line Parameter Default Range
S501 Password - -
S502 Number of Standby Units 0 0 – 15
S503 Rotation Frequency No
No, Daily, Every M,
T, W, Th, F, S, Su
S504 Rotate at (hour) 0 0 – 23
S505 Rotate at (minute) 0 0 – 59
S506 Rotate by 1 1 – 8
S507 Perform one rotation - No or Yes
S508 Cascade units No
No, Yes, Cool,
Temp
S509 Start All Standby Units by HT No No or Yes
S510
S511
Service Menu: General Settings Maintenance / Wellness Parameters S000
series: Page 1 of 8
Menu Line Parameter Default Range
S001 Password - -
S002 Maintenance Frequency Per Year 1
0 – 12 per
year
S003 Max Bonus 0 0 – 12
S004 Max Penalty 0 0 – 12
S005 Last Maintenance - Date
S006 Service Engineer - Name
S007 Confirm PM - No or Yes
S008 Calculated Next Maintenance - Date
69