Disassembling the Liebert DS for Transport
53
Figure 43 Component dimensions—downflow, air-cooled, 105kW (30 ton), semi-hermetic compressor
models
Table 33 Component weights—downflow, air-cooled, 105kW (30 ton), semi-hermetic compressors
Component
Dry Weight, lb (kg) Approximate (Includes Panels)
Air Cooled Dual Cool
Compressor Assembly 950 (432) 950 (432)
Filter & Electric Box Assembly 270 (123) 270 (123)
Blower & Coil Assembly 1820 (827) 2180 (991)
37"
(940mm)
59-7/16"
(1510mm)
DPN001057
Rev. 0
131" (3327mm)
Assembled Length
33"
(838mm)
26"
(660mm)
105"
(2667mm)
76"
(1930mm)
39"
(991mm)
41-11/16"
(1059mm)
Filter and Electric Box Assembly
Compressor Assembly
Blower and Coil Assembly
76"
1930mm
Assembled
Height
Vista de pagina 62