Disassembling the Liebert DS for Transport
50
Figure 40 Component dimensions—downflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic
compressor models
Table 30 Component weights—downflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic
Dry Weight, Approximate, Including Panels, lb (kg)
Component
Air-Cooled Dual-Cool
Compressor Assembly 970 (441) 970 (441)
Filter & Electric Box Assembly 250 (114) 250 (114)
Blower & Coil Assembly 1230 (560) 1410 (641)
82" (2083mm)
DPN000926
Rev. 2
33"
(838mm)
26"
(660mm)
76"
(1930mm)
108" (2743mm)
Assembled Length
76"
(1930mm)
Assembled
Height
59-7/16"
(1509mm)
37"
(940mm)
39"
(991mm)
Compressor Assembly
Filter & Electric
Box Assembly
Blower & Coil
Assembly
NOTES: Drawing views are simplified with panels removed to show overall dimensions.