Liebert PDUTM Manual de usuario Pagina 20

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 156
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 19
Power and Control Wiring
12
4.5 Power Supply
The STS2/PDU is supplied with redundant power supplies that are designed to operate from a voltage
range of 200V to 600V. The unit is set at the factory to match the nameplate voltage. Field adjust-
ments are not necessary. If the unit needs to operate at a voltage other than what is listed on the
nameplate, contact Liebert Global Services or your local Liebert representative. Table 6 provides
transformer tap information.
Table 6 Terminal block 1 and terminal block 2 wire connections
Voltage
Connect Connect
Jumper BetweenF1 TB1-XX F2 TB1-YY F3 TB2-XX F4 TB2-YY
200 1 9 1 9 1-7
220 2 12 2 12 6-8
3801818 2-7
415 1 10 1 10 4-7
600 1 12 1 12 6-7
208 1 10 1 10 1-7
240 1 11 1 11 1-7
400 1 9 1 9 3-7
480 1 11 1 11 5-7
!
CAUTION
Using Table 6, ensure that the wiring for the control transformers matches the input voltage
for the unit.
Improper wiring could result in blown fuses.
Vista de pagina 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 155 156

Comentarios a estos manuales

Sin comentarios